Effects of unbalanced power distribution on the neutral line
It’s clear that one of the most common electric businesses
is electric distribution for residential, commercial and industrial buildings.
And as a rule of thumb all residential buildings have three-phase wye supply
and also nearly most of small commercial and industrial facilities. Speaking
about wye connection we expect that all three phases have about the same amount
of current and the neutral have a very little current, this case is called a balanced
system.
The most common case is to have a balanced system but
sometimes it happens to have an unbalanced system and then a current pass in
the neutral cable. So, we will discuss the cases which lead to have a high
current in the neutral, how this affects the neutral and how to solve this situation
to keep the wiring safe.
Unbalanced distribution of loads
Usually in commercial and residential buildings most of
loads are single-phase but the main feeders to the building are three phases. So,
phase scheduling is done to balance these single-phase loads on the three phase
supply so we have a balanced system.
As living style changes constantly so loads also changes,
just imagine that many of your neighbours install new heavy-duty appliances
like air conditioners and assume the added loads is on phase A only. Now our
system is not balanced anymore Thus the neutral cable will have high amount of
current due to the vector sum of all currents is not equal to zero.
Zero sequence harmonics
Power electronics devices is a double-edged sword, it made
life easier in many fields for example power supplies, variable speed drives
and also computer devices. These devices are considered as non-linear loads and
its current contains a lot of harmonics.
These harmonics are divided into 3 types, zero sequence,
negative sequence and positive sequence. The zero sequence currents are in
phase and the vector sum of them can be considered as algebraic sum, these
currents pass through the neutral.
So if we have a zero sequence component equal to 30 ampere
then the neutral will have 90 ampere current, which maybe lead to overloading
it.
The effect on neutral cable and solutions
1. Usually
in electrical distribution for residential buildings, the cross-section area of
neutral wire is half of the hot wires. So, its current carrying capacity is
smaller and surely won’t be able to carry as much as the hot wires’ current.
In case of unbalanced loading, the neutral wire will have
amount of current passing through it. If this current is higher than wire
capacity then it will be burnt and we’ll have power outage till neutral wire is
replaced.
Now we have two ways to fix and prevent this problem to
arise. The first is to size the neutral wire as same as hot wires, and this
will reduce the possibility of having the neutral overloaded and burnt. Second
way is to reschedule the loads and balance it on the 3 phases then neutral
current will be nearly zero and this is optimal case.
2. In
industrial and commercial buildings, we find the common loads are motors which
requires variable speed drives and many computers which are sources of
harmonics, that’s why the neutral is always full wire. And with the presence of
zero sequence harmonics the neutral will be overloaded and maybe burnt.
Solution for such case is to use filters to act as high
impedance in front of harmonics current and so neutral current will be nearly
zero and no harm happens.
Conclusion
It’s obvious that continues monitoring for your utility is a
recommended behavior to check the load balance and measure the level of
harmonics and its current value to keep your utility safe and prevent
discontinuity of service as much as we can.
Originally Publish at: http://engineering.electrical-equipment.org/